ATC-003_Config_Update_Applies_Within_Bounds
Validate valid configuration writes are accepted and applied by control logic.
Execution
Field |
Value |
|---|---|
Status |
pass |
Test Type |
functional_acceptance |
Last Run At |
2026-02-28T17:04:15Z |
Last Runner |
Baseline_Verification |
Preconditions
Runtime is active and writable configuration registers are reachable through the communication path.
Procedure
Write a valid set of threshold and hysteresis values. Read back active values and run a short thermal stimulus to confirm behaviour follows updated parameters.
Expected Result
Valid configuration writes are accepted applied and reflected by subsequent control behaviour without violating defined limits.
Traceability
Element Type |
Referenced Elements |
|---|---|
Requirements |